Description
Installation Handbook, AutroFlame X33AF PL Multispectrum IR Flame Detector, 116-P-X33AF/PL/DE, 2005-12-12,
Autronica Fire and Security AS
Page 5
2.1 LED
A tricolor LED on the detector faceplate indicates normal, fire alarm
and fault conditions. Table 2 indicates the condition of the LED for
each detector status.
Detector Status LED indicator
Power On/Normal Operation
(No fault or fire alarm)
Green
Fault Amber
Fire (Alarm) Red
Medium Sensitivity
Two Amber Flashes
During Power-up
Very High Sensitivity
Four Amber Flashes
During Power-up
2.2 Optical Integrity (Oi)
2.2.1 Automatic Oi
The X33AF PL includes the Automatic Optical Integrity (oi) feature - a
calibrated performance test that is automatically performed once per
minute to verify complete detector operation capabilities. No testing
with an external test lamp is required. The detector automatically
performs the same test that a maintenance person with a test lamp
would perform - once every minute, 60 times per hour. A successful
automatic of test does not produce an alarm condition.
The X33AF PL signals a fault condition when less than 50% of the
detection range remains. This is indicated by the yellow colour of the
LED on the face of the detector. See the “Troubleshooting” section for
further information.